Clay pipe adapter
-
- Posts: 9
- Joined: Wed May 31, 2017 5:56 pm
- Location: Birmingham
Hello all,
I am trying to connect some 110mm plastic under ground pipe to the existing clay pipe for a toilet connection.
We have done quite a lot of drainage before on jobs but this one is a problem. Normally we make the connection with a flexible rubber adapter. This time though most of the pipe is surrounded in concrete.
Is there any type of internal fitting that can be used ie from a socket on the plastic pipe to the internal of the clay pipe as we have managed to remove a section of existing clay pipe from it socket?
Hope this makes sense
I am trying to connect some 110mm plastic under ground pipe to the existing clay pipe for a toilet connection.
We have done quite a lot of drainage before on jobs but this one is a problem. Normally we make the connection with a flexible rubber adapter. This time though most of the pipe is surrounded in concrete.
Is there any type of internal fitting that can be used ie from a socket on the plastic pipe to the internal of the clay pipe as we have managed to remove a section of existing clay pipe from it socket?
Hope this makes sense
-
- Posts: 2504
- Joined: Thu Jul 10, 2003 10:20 pm
- Location: hemel hempstead,herts. 01442 212315
Last time I came across this, I chiseled the concrete off using an sds, revealed about 6inch of pipe then used the rubber adaptor. not sure if you can insert a plastic pipe inside a clay joiner piece?
Dan the Crusher Man
01442 212315
www.crusherhire.co.uk
"a satisfied customer? we should have them stuffed!"
01442 212315
www.crusherhire.co.uk
"a satisfied customer? we should have them stuffed!"
-
- Site Admin
- Posts: 4713
- Joined: Mon Jun 26, 2006 11:01 am
- Location: eastbourne
Yes you can get an adaptor that pushes inside the clay pipe . Osma do one but can't remember part number. I should think you could pick one up at
Builders merchant. It has a rubber spigot that seals the inside of the pipe and a push in collar as normal. Bit like the one that goes into back of toilet.
Builders merchant. It has a rubber spigot that seals the inside of the pipe and a push in collar as normal. Bit like the one that goes into back of toilet.
sean
-
- Posts: 9
- Joined: Wed May 31, 2017 5:56 pm
- Location: Birmingham
-
- Posts: 186
- Joined: Thu Jul 01, 2010 6:50 pm
- Location: manchester
-
- Site Admin
- Posts: 4713
- Joined: Mon Jun 26, 2006 11:01 am
- Location: eastbourne
-
- Site Admin
- Posts: 15184
- Joined: Fri Aug 04, 2006 12:20 am
- Location: bedfordshire
-
- Site Admin
- Posts: 4713
- Joined: Mon Jun 26, 2006 11:01 am
- Location: eastbourne
I have used the Mc Alpine DC1BL before now. This one is recommended by J Atkinson for low level drainage. Breaking around the pipe can be done if you go careful, may take some time but the old clay are so brittle. They aren't very long, about 2 ft so you could break back to the collar, take out the yarn and re-make the joint.
sean
-
- Site Admin
- Posts: 15184
- Joined: Fri Aug 04, 2006 12:20 am
- Location: bedfordshire
Great advice Sean, the other option is to get the pipe patch lined so you butt your new pipe up and Davy Brown or one of his people patch lines it,
I still have nightmare about a job in hemel where we ended up going 3 metres back to the IC ,the concrete was as strong and solid as it could be and the pipe just kept breaking
LLL
I still have nightmare about a job in hemel where we ended up going 3 metres back to the IC ,the concrete was as strong and solid as it could be and the pipe just kept breaking
LLL
-
- Posts: 9
- Joined: Wed May 31, 2017 5:56 pm
- Location: Birmingham
That is the fitting we tried. Building Inspector would not allow as he said it is not what the fitting is designed for & the internal diameter reduces to around 80mm.seanandruby wrote:I have used the Mc Alpine DC1BL before now. This one is recommended by J Atkinson for low level drainage. Breaking around the pipe can be done if you go careful, may take some time but the old clay are so brittle. They aren't very long, about 2 ft so you could break back to the collar, take out the yarn and re-make the joint.
-
- Posts: 2504
- Joined: Thu Jul 10, 2003 10:20 pm
- Location: hemel hempstead,herts. 01442 212315
Was that cowper road, where I turned up an met flowjoe? ( whatever happened to him?)lutonlagerlout wrote:Great advice Sean, the other option is to get the pipe patch lined so you butt your new pipe up and Davy Brown or one of his people patch lines it,
I still have nightmare about a job in hemel where we ended up going 3 metres back to the IC ,the concrete was as strong and solid as it could be and the pipe just kept breaking
LLL
Dan the Crusher Man
01442 212315
www.crusherhire.co.uk
"a satisfied customer? we should have them stuffed!"
01442 212315
www.crusherhire.co.uk
"a satisfied customer? we should have them stuffed!"
-