Adding a new pipe to an existing soakaway

Foul and surface water, private drains and public sewers, land drains and soakaways, filter drains and any other ways of getting rid of water.
Post Reply
RogGriffin
Posts: 4
Joined: Thu Apr 13, 2006 8:29 pm
Location: Dorset, UK

Post: # 11530Post RogGriffin

Hi,
I am in the process of building a new detached apex garage and have a question regarding the rain water drainage from the roof. We have an existing soakaway which is used for some of the guttering of the house. Is there any problem with directing the guttering from the new garage into the existing soakaway by adding an extra feed pipe into the soakaway?
Thanks

Tony McC
Site Admin
Posts: 8346
Joined: Mon Jul 05, 2004 7:27 pm
Location: Warrington, People's Republic of South Lancashire
Contact:

Post: # 11542Post Tony McC

As long as the soakaway can cope with the additional input, no problem at all.
Site Agent - Pavingexpert

RogGriffin
Posts: 4
Joined: Thu Apr 13, 2006 8:29 pm
Location: Dorset, UK

Post: # 11758Post RogGriffin

OK,
I have now located a 110mm Orange plastic pipe that goes into the soakaway.
Can I connect downpipe directly into the 110mm pipe, via a boss or some other method, if so could you tell me how ?
Thanks

Mark B
Posts: 86
Joined: Fri Feb 24, 2006 12:37 am
Location: Hamilton, Scotland

Post: # 11762Post Mark B

since its not foul waste water, there is probably no need for a trap, so the rain water pipe can be directly conected to the 110mm dia pipe using either a hopper, or there is some other reduction piece avaliable that would allow a rain water pipe to connect to the 110mm dia pipe.

RogGriffin
Posts: 4
Joined: Thu Apr 13, 2006 8:29 pm
Location: Dorset, UK

Post: # 11776Post RogGriffin

OK. But is there any reason why I can't take the 68mm downpipe underground for a few metres (approx 4m) to then join onto the 110mm underground pipe using one of the reduction pieces ?

This would save having to lay a small run of 110mm underground pipe.
Thanks

Tony McC
Site Admin
Posts: 8346
Joined: Mon Jul 05, 2004 7:27 pm
Location: Warrington, People's Republic of South Lancashire
Contact:

Post: # 11799Post Tony McC

68mm pipe isn't strong enough to be buried. It will deform. It's up to you to decide whether it's worth the risk.
Site Agent - Pavingexpert

RogGriffin
Posts: 4
Joined: Thu Apr 13, 2006 8:29 pm
Location: Dorset, UK

Post: # 11804Post RogGriffin

Thanks. I assume that there are no building regs about this then ?

Tony McC
Site Admin
Posts: 8346
Joined: Mon Jul 05, 2004 7:27 pm
Location: Warrington, People's Republic of South Lancashire
Contact:

Post: # 11831Post Tony McC

Building Regs require drainage to be 100mm diameter as a minimum.
Site Agent - Pavingexpert

Post Reply