Off-set bend

Foul and surface water, private drains and public sewers, land drains and soakaways, filter drains and any other ways of getting rid of water.
Post Reply
alistair.greenhough
Posts: 2
Joined: Thu Jul 07, 2011 8:15 pm
Location: york

Post: # 65856Post alistair.greenhough

I am puting in an inspection chamber with one pipe run coming in and one going out. In order to get my incoming pipe in the right direction am I allowed to put an off-set elbow coming off the inspection chamber to direct the straight run in the right direction? A rodable gully is going on the other end.
alistair greenhough

seanandruby
Site Admin
Posts: 4713
Joined: Mon Jun 26, 2006 11:01 am
Location: eastbourne

Post: # 65864Post seanandruby

any bends must be inside, or as close as possible to the manhole/inspection chamber. So yes it's ok.
sean

local patios and driveway
Posts: 1568
Joined: Mon May 10, 2010 9:58 pm
Location: Gatwick
Contact:

Post: # 65866Post local patios and driveway

ideally your bend should be on the pipe coming in to the chamber not the pipe leaving

lutonlagerlout
Site Admin
Posts: 15184
Joined: Fri Aug 04, 2006 12:20 am
Location: bedfordshire

Post: # 65869Post lutonlagerlout

both of the above are spot on
the pipe leaving should always be connected to the channel,and any bend should be as slight as possible i.e. 15 deg or 30 deg max
BCOs dont like what they cant see
LLL
"what,you want paying today??"

YOUR TEXT GOES HERE

alistair.greenhough
Posts: 2
Joined: Thu Jul 07, 2011 8:15 pm
Location: york

Post: # 65930Post alistair.greenhough

Ok Thanks.