How much fall will i need - foul drain for toilet?

Foul and surface water, private drains and public sewers, land drains and soakaways, filter drains and any other ways of getting rid of water.
Post Reply
bert
Posts: 32
Joined: Sat May 08, 2010 12:54 am
Location: suffolk

Post: # 55163Post bert

ive got a 27 meter run with two 90 bends in it , its a combined toilet , bath and basin with one rainwater all running into a sewer.
what would the total fall be that i need guys? do the 90 bends make a difference?
ive got 550 mm to play with from toilet position to man hole, is this too tight?
restoring a 16c cottage , slowly.

mickg
Posts: 2598
Joined: Wed Apr 08, 2009 8:01 am
Location: Peoples Republic of Westhoughton
Contact:

Post: # 55166Post mickg

by my reckoning with your distance of 27 metres and 550mm depth to play with the fall is 1:48.63

you needed 668.65mm depth so your fall is 4.394mm per metre in length less than it should be at 1:40 (thats 1 inch fall for every 40 inch of length) for a foul drain so yeah its tight on fall but with modern day plastic pipe and push fittings it should not be a problem

Disclaimer
no liability is accepted for the above comment ???

make sure you use the correct lubrication and to chamfer any cut lengths of pipe so you don't damage the rubber seal when you push the pipe into the bends or straight connectors

I have seen many a salt glazed pipe not properly jointed and cleaned off with a richard the third stuck on the snot of mortar, if plastic underground drainage is install correctly then this is a thing of the past :)
Crystalclear
Driveway and Patio Installer

Call us today
01942 840109
7 days a week 8am till 8pm

Driveways Patios and Paving Specialists
Driveways

lutonlagerlout
Site Admin
Posts: 15184
Joined: Fri Aug 04, 2006 12:20 am
Location: bedfordshire

Post: # 55173Post lutonlagerlout

bert no building inspector will pass a foul run with 90 deg bends in it
if you have to turn 90 deg they want an inspection chamber
plus with a 27m run it would be prudent to have a couple of ICs
these would do the trick
LLL
"what,you want paying today??"

YOUR TEXT GOES HERE

GB_Groundworks
Site Admin
Posts: 4420
Joined: Sat Aug 09, 2008 3:55 pm
Location: high peak
Contact:

Post: # 55174Post GB_Groundworks

Most bco will let you get away with less fall if the run is in 150mm but must convert between 110mm and 150mm within an ic or man hole,

On your 90 you will need to use the 330mm 90 degree inspection chambers for any change of direction

Haha my boy was pestering to play monkey lunch box on my iPad as I typed that haha or I'd have beat you lol.

I'd get a level as well either laser or automatic level to confirm your falls




Edited By GB_Groundworks on 1286993159
Giles

Groundworks and Equestrian specialists, prestige new builds and sports pitches. High Peak, Cheshire, South Yorkshire area.

http://www.gbgroundworks.com

lutonlagerlout
Site Admin
Posts: 15184
Joined: Fri Aug 04, 2006 12:20 am
Location: bedfordshire

Post: # 55175Post lutonlagerlout

if you snooze you lose!
LLL :;):




Edited By lutonlagerlout on 1286993865
"what,you want paying today??"

YOUR TEXT GOES HERE

bert
Posts: 32
Joined: Sat May 08, 2010 12:54 am
Location: suffolk

Post: # 55178Post bert

thanks guys , i used string and a 1 meter level so my measurements wont be perfect but i can raise the floor level a bit if i have to to compensate.
i probably wont be doing the work my self , well that is if i can afford to pay someone to do it for me. any ideas of how much a job like this would cost?
also , if the room was a bathroom before the renovation work but it didnt have a wc in there would i need a change of use planning application? or would it be best just not to tell anyone? :;):
restoring a 16c cottage , slowly.

flowjoe
Posts: 1136
Joined: Sun May 08, 2005 9:25 am
Location: North West

Post: # 55179Post flowjoe

:;):
http://draindomain.com

Many paths can lead to riches, few in sunlight, some in ditches