Retaining wall - Dpc and land drain

Other groundworks tasks, such as roads and footpaths, terracing, fencing, foundations, walls and brickwork, tools and plant.
Post Reply
Richey
Posts: 21
Joined: Wed Jan 16, 2008 8:05 pm
Location: Waltham Forest

Post: # 26963Post Richey

Hi, have just finished reading all about retaining walls and still need a little help!

Does the 80mm diameter collector drain at the base of the wall need to flow into a catch basin or soak away or is it just there behind the wall acting as a sump to relieve the wall from a build up of water pressure. Naturally I will be including weep holes when I come to building my wall.

Why does a free standing wall need a damp proof course? What am I protecting by including one? And is anything bonding the course of bricks directly below the dpc membrane to the rest of the wall apart from the weight of the bricks above?

Finally...Is a dpc needed if using Marshalite Walling Blocks? I've never seen one.

Thanks to anyone who replies

Richey

matt h
Posts: 607
Joined: Mon Jul 09, 2007 11:14 pm
Location: gosport

Post: # 26964Post matt h

The answer to your questions is yes,
stops water rising up the wall and eventually weakening the wall through frost damage etc
DPC is bonded to both courses above and below and is assisted by the weight of the courses above, and marshalite blocks should have dpc course, but have seen several garden divider walls constructed without them
general builder, maintenance engineer, gas and plumbing installations, extensions etc

lutonlagerlout
Site Admin
Posts: 15184
Joined: Fri Aug 04, 2006 12:20 am
Location: bedfordshire

Post: # 26970Post lutonlagerlout

Icould be wrong,and i have built maybe a 100+ retaining walls but i have never put a dpc in one yet.
we use sulphate resisting cement 3:1 ,but why would we need dpc in a free-standing wall that is subject to the elements?

obviously you need an f1 or f2 brick or walling block for retaining walls.
it breaks my heart when i see walls built with LBCs, there is a particular one in luton that was built about a year ago,its cracked already and i am waiting for the frost to get hold of it,when i replace my cybershot i will take a photie of the imminent failure
cheers LLL
"what,you want paying today??"

YOUR TEXT GOES HERE

Rich H
Posts: 884
Joined: Thu Feb 08, 2007 12:28 pm
Location: Reading

Post: # 26986Post Rich H

Tony, you'll probably not be pleased to hear that I've built another LBC wall in the same street as the last one! The customer asked me to build them a drive just like the one up the street! And I repaired the neighbour's wall. I did at least explain that the same would happen to the walls in time, but they both wanted to keep the look as before...

lutonlagerlout
Site Admin
Posts: 15184
Joined: Fri Aug 04, 2006 12:20 am
Location: bedfordshire

Post: # 27022Post lutonlagerlout

i consign you to hellfire and eternal damnation rich!!

you can lead a horse to water, but you cant make it drink

at least your way it will give a brickie some work in 10 years time :D

LLL
"what,you want paying today??"

YOUR TEXT GOES HERE

Rich H
Posts: 884
Joined: Thu Feb 08, 2007 12:28 pm
Location: Reading

Post: # 27035Post Rich H

You see, every ones a winner :D

Richey
Posts: 21
Joined: Wed Jan 16, 2008 8:05 pm
Location: Waltham Forest

Post: # 27042Post Richey

Thanks for all the replies, however thickie here still doesn't quite get it.
Matt, when you said "The answer is yes" what were you saying yes to... that there MUST be a catch basin/soak away, or Yes the pipe can relieve the water pressure off the wall in its own right without the need for a catch basin/soak away.

Sorry to be a pain
Cheers

Richey

Rich H
Posts: 884
Joined: Thu Feb 08, 2007 12:28 pm
Location: Reading

Post: # 27054Post Rich H

The perforated pipe needs to be laid to a gradient allowing water to flow along its length. At the end, the discharge needs to go somewhere, preferably a properly constructed soakaway.

I've also never built a retaining wall without a membrane.

lutonlagerlout
Site Admin
Posts: 15184
Joined: Fri Aug 04, 2006 12:20 am
Location: bedfordshire

Post: # 27056Post lutonlagerlout

i have used membrane vertically when specified, but the point of a dpc in an out door wall baffles me??

what will it do?

LLL :;):
"what,you want paying today??"

YOUR TEXT GOES HERE

seanandruby
Site Admin
Posts: 4713
Joined: Mon Jun 26, 2006 11:01 am
Location: eastbourne

Post: # 27057Post seanandruby

......weaken it at dpc level i would of thought :laugh:
sean

lutonlagerlout
Site Admin
Posts: 15184
Joined: Fri Aug 04, 2006 12:20 am
Location: bedfordshire

Post: # 27068Post lutonlagerlout

exactamundo sean!
LLL :;):
"what,you want paying today??"

YOUR TEXT GOES HERE

seanandruby
Site Admin
Posts: 4713
Joined: Mon Jun 26, 2006 11:01 am
Location: eastbourne

Post: # 27071Post seanandruby

seen them pushed out and ready to topple with ground heave. got a photo of one somewhere i'll look it out.
sean

Richey
Posts: 21
Joined: Wed Jan 16, 2008 8:05 pm
Location: Waltham Forest

Post: # 27138Post Richey

Thanks, that's much clearer. Will definately be using a membrane. Here's the tricky bit about building a soak away/catch basin at the end of the drainage pipe... the retaining wall will go right across the garden from fence to fence so there will be no room for a soak away at either end which means I'll have to bend the pipe round to either in front of the wall or behind it. Draining water away to behind the wall would be silly as surely the water would make its way towards the wall again?? Not to mention the depth of hole I would have to dig. That leaves digging a soak away in front of the wall. Fine, only I want a patio there. Is it ok to pave over a soakaway? Does any one have any thoughts on the best place to build this soakaway? (apart from into the neighbours garden) :D

Cheers Richey

Rich H
Posts: 884
Joined: Thu Feb 08, 2007 12:28 pm
Location: Reading

Post: # 27143Post Rich H

Whoops - I typed without when I meant with. Damned double negatives.

Just to clarify.

Retaining wall = no dpc for me.

Post Reply