250mm or 450mm inspection chamber / mh - Which size??

Foul and surface water, private drains and public sewers, land drains and soakaways, filter drains and any other ways of getting rid of water.
Post Reply
100-1171570483

Post: # 16604Post 100-1171570483

Hi All

I'm adding first floor extension with en-suite, and I need to branch into the existing soil pipe under ground level @ 550mm deep (existing SVP is build inside the house so can't tee into above ground level) I've ready exposed the existing SVP under ground and is ready to install new inspection chamber....Which Size??

I would like to use 250mm IC because it cheaper / neater BUT... What I don't want to happen is; I install 250mm inspection chamber and Building control knock it back because I used the wrong size.

Thanks for your help

flowjoe
Posts: 1136
Joined: Sun May 08, 2005 9:25 am
Location: North West

Post: # 16605Post flowjoe

250mm is fine to an invert depth of 600mm
http://draindomain.com