New connection to drain - My bad

Foul and surface water, private drains and public sewers, land drains and soakaways, filter drains and any other ways of getting rid of water.
Post Reply
roadster1
Posts: 5
Joined: Thu Apr 06, 2006 9:38 am
Location: (deep in the wilds of) Leicestershire

Post: # 11390Post roadster1

First Post!

I have just about finished converting my cellar into a utility room but have made a bit of a c0ck up :(

When the house was renovated / extended the builder installed a large diameter pipe from the cellar, under the kitchen (solid floor) to an air brick in the kitchen wall to provide ventilation. I am running the outlet of the Sanivite pump (32mm plastic) through this to the drain. However due to my mistake in measuring.............when I knocked out the air brick I found this
Image

The pipe is actually 8 inches lower than I thought (How embarassing!)

The inspection cover is close by

Image

Image

Image

As the outlet pipe is now too low to go into the existing drain what can I do to be saved??

Great site by the way!

Howard
Retired Computer Engineer.

Why pay someone to do something when you can learn how to do it yourself?

flowjoe
Posts: 1136
Joined: Sun May 08, 2005 9:25 am
Location: North West

Post: # 11398Post flowjoe

Hard to tell from here but eight inch below the air-brick will be ground level won`t it.

Can`t you core drill through into the air vent and let the pump lift the waste into the gully via a couple of bends, you will have to check the installation bumpth about number of bends allowed and how this will affect the total lift capacity.

If not you are looking at an excavation and new branch onto the existing drainage system, but you will still have to core-drill thru to your pipe.




Edited By flowjoe on 1144345300
http://draindomain.com

Many paths can lead to riches, few in sunlight, some in ditches

roadster1
Posts: 5
Joined: Thu Apr 06, 2006 9:38 am
Location: (deep in the wilds of) Leicestershire

Post: # 11403Post roadster1

Thanks for the reply.
eight inch below the air-brick will be ground level won`t it

Yes or a couple of inches below.
let the pump lift the waste into the gully

All the vertical lift has to be at the pump end.

It does look like I will have to put in a new branch into the existing drain and thats where my experience ends........ I've looked at the Marley catalogue on line, what is the way to go? Should I position the new gully/trap below ground level and form the opening at ground level in brick/mortar or is there a fitting available to do this? What should I use to connect into the existing drain?
Retired Computer Engineer.

Why pay someone to do something when you can learn how to do it yourself?

flowjoe
Posts: 1136
Joined: Sun May 08, 2005 9:25 am
Location: North West

Post: # 11412Post flowjoe

There are pages within the main site showing how to connect a new junction into an existing section of pipe work.

I would then run a branchline across to the air brick (approx) and fit a back inlet gully, this means that the gully has a water trap to stop smells venting from the main system, but it also has a 100mm inlet higher than the water level but below ground level (approx 150mm), You can then get an insert/boss fitting to connect the 32mm to the 100mm inlet that will remain water and air tight.

Scroll down the following page and you will find the type of gully and boss fitting required.

http://www.fascias.com/en-gb/dept_48.html

Tony may have aready covered this on the drainage pages
http://draindomain.com

Many paths can lead to riches, few in sunlight, some in ditches

roadster1
Posts: 5
Joined: Thu Apr 06, 2006 9:38 am
Location: (deep in the wilds of) Leicestershire

Post: # 11420Post roadster1

That's brilliant. Thanks very much. :) :)

Howard
Retired Computer Engineer.

Why pay someone to do something when you can learn how to do it yourself?

roadster1
Posts: 5
Joined: Thu Apr 06, 2006 9:38 am
Location: (deep in the wilds of) Leicestershire

Post: # 11569Post roadster1

Image

Image

Here is where I'm up to.......The yellow blob indicates where the 32mm pipe will come out.

As you can see space is limited and there is not enough room for a back inlet gully.

Would it be practical to replace the bend with a "T" Junction and an adapter ?? If I use a universal adapter does it give some flexibility for the angle as the pipe enters it?
Retired Computer Engineer.

Why pay someone to do something when you can learn how to do it yourself?

flowjoe
Posts: 1136
Joined: Sun May 08, 2005 9:25 am
Location: North West

Post: # 11573Post flowjoe

Looks like a nice soft sub-soil you are playing in roadster :laugh:

You will have to follow the pipe work for at least 500mm if not more, it looks as though it is bending and dropping at the same time which will give you more room to play in.

Why don`t you remove the existing gully pot, install a back inlet gully as required and then plumb your kitchen waste and rainwater downspout into the new back inlet gully.
http://draindomain.com

Many paths can lead to riches, few in sunlight, some in ditches

roadster1
Posts: 5
Joined: Thu Apr 06, 2006 9:38 am
Location: (deep in the wilds of) Leicestershire

Post: # 11574Post roadster1

Time to hire a breaker me thinks. We hate those cobbles anyway, so 2 jobs in one :)

Thanks for the help.
Retired Computer Engineer.

Why pay someone to do something when you can learn how to do it yourself?