Can a drain be *too* steep?

Foul and surface water, private drains and public sewers, land drains and soakaways, filter drains and any other ways of getting rid of water.
Post Reply
Crofter
Posts: 5
Joined: Wed Jan 14, 2015 1:09 pm
Location: Highland

Post: # 102377Post Crofter

I need to make a fall of about 6m over a distance of 34m, to connect my house to a new septic tank system.
I'm aware that there are regulations covering minimum gradient, 1:80 I believe, but I can't find anything about a maximum gradient. It has been mentioned to me that beyond a certain gradient you risk 'stranded solids' however I cannot find what that magic gradient might be, and any attempts to google it simply turn up people declaring the whole thing to be a myth anyway, suggesting you can go for whatever gradient you want.

I did email my BCO but he only said to keep the fall into the tank at 1:40, and use backdrop manholes. I can understand that the final flow into the tank needs to be at a low rate, but I don't see why it matters what I do upstream of that.

Part H has tables showing flow rates starting at 1:10 which whilst not stated as being any sort of limit at least implies that you can go that steep.
If I can go to 1:6 or so then it will save me a lot of hassle building backdrop manholes.

Cheers

seanandruby
Site Admin
Posts: 4713
Joined: Mon Jun 26, 2006 11:01 am
Location: eastbourne

Post: # 102379Post seanandruby

Anything less than a 1:10 should go into a back drop.
sean

lutonlagerlout
Site Admin
Posts: 15184
Joined: Fri Aug 04, 2006 12:20 am
Location: bedfordshire

Post: # 102384Post lutonlagerlout

they really dont like anything too steep or separation will occur
as said we normaly keep between 1:30-1:50 and use roddable back drops
LLL
"what,you want paying today??"

YOUR TEXT GOES HERE

Crofter
Posts: 5
Joined: Wed Jan 14, 2015 1:09 pm
Location: Highland

Post: # 102385Post Crofter

Thanks, it seems there's no actual regulation on this, just good/best/accepted practise.

I got another reply from BCO which indicated 1:10 ought not to be a problem, he mentioned modern plastic pipes as being an advantage, I presume that is because they are smooth?

There will need to be some chambers at changes of direction, so I can incorporate some fall there, just don't want to do all 6m that way :)

Captain Concrete
Posts: 77
Joined: Fri Oct 31, 2014 7:35 am
Location: southeast
Contact:

Post: # 102561Post Captain Concrete

You could keep the drain fairly shallow then use a Mascar bowl as a back drop, we've done this many times and Mascar bowls are fantastic for this and have never given us problems.
Been in concreting for 22 years